33kv Uganda S/C 185mm2 240mm2 Three core Power Cable Standards:
IEC 60502 Part 2(3.6/6KV to 18/30KV),BS6022
33kv Uganda S/C 185mm2 240mm2 Three core Power Cable Application:
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 1.8/3KV to 26/35KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
33kv Uganda S/C 185mm2 240mm2 Three core Power Cable Construction:
Conductor: Plain annealed copper or aluminium complying with IEC 60228 class 2.
Conductor Screen: extruded layer of semi-conducting crosslink compound
Insulation: Insulation is of polyvinyl chloride (PVC) intended for 1.8/3.6KV and 3.6/6KV cables, cross-linked polyethylene compound (XLPE)
Nom. Cross Section Area |
Insulation Thickness at Nominal Voltage |
1.8/3KV |
3.6/6KV |
6/10KV |
8.7/15KV |
12/20KV |
18/30KV |
21/35KV |
26/35KV |
(Um=3.6KV) |
(Um=7.2KV) |
(Um=12KV) |
(Um=17.5KV) |
(Um=24KV) |
(Um=36KV) |
(Um=42KV) |
(Um=42KV) |
mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
|
XLPE |
XLPE |
XLPE |
XLPE |
XLPE |
XLPE |
XLPE |
XLPE |
10 |
2 |
2.5 |
- |
- |
- |
- |
- |
- |
16 |
2 |
2.5 |
3.4 |
- |
- |
- |
- |
- |
25 |
2 |
2.5 |
3.4 |
4.5 |
- |
- |
- |
- |
35 |
2 |
2.5 |
3.4 |
4.5 |
5.5 |
- |
- |
- |
50 - 185 |
2 |
2.5 |
3.4 |
4.5 |
5.5 |
8 |
9.3 |
10.5 |
240 |
2 |
2.6 |
3.4 |
4.5 |
5.5 |
8 |
9.3 |
10.5 |
300 |
2 |
2.8 |
3.4 |
4.5 |
5.5 |
8 |
9.3 |
10.5 |
400 |
2 |
3 |
3.4 |
4.5 |
5.5 |
8 |
9.3 |
10.5 |
500 - 1600 |
2.2-2.8 |
3.2 |
3.4 |
4.5 |
5.5 |
8 |
9.3 |
10.5 |
Insulaton Screen: extruded layer of semi-conducting cross-link compound
Metallic Screen:Copper tape screen or copper wire with helically copper tape
Separation Sheath (for armoured cable): extruded PVC, PE or LSZH, applied under the armour .
Lapped Bedding : The lapped bedding consists of Polyester non woven fabrics .
Armour (for armoured cable): It consists of either flat galvanized steel wire armour (strip), round galvanized steel wire armour, and double steel tape armour.
Outer Sheath: PVC, PE, HDPE, MDPE or LSZH
Installation and operation condition of cable:
Operating Temperature: up to 90°C
Short Circuit Temperature( 5 seconds maximum duration ): 250°C
Bending Radius: 12 x OD
Current Rating Conditions:
Ground Temperature: 20°C
Ambient Temperature (air): 30°C
Depth of Soil: 0.8m
Thermal Resistance of Soil: 1.5K•m/W
Rated Voltage Uo/U |
Operating Voltage (Um) |
Testing Voltage
(rms) |
19/33KV |
36KV |
76KV |
Dimensional Data:
Nom.Cross-Section Area |
|
Unarmoured Cables |
Steel Wire Armoured Cables |
Nom.Insulation Thickness |
Copper Wire Screen Area |
Nom. |
Approx. Overall Diameter |
Approx. Weight |
Copper Tape Screen Area |
Nom. |
Nom. Armour Wire Diameter |
Nom. |
Approx. Overall Diameter |
Approx. |
Sheath |
Bedding |
Sheath Thickness |
Weight |
|
Thickness |
CU |
AL |
Thickness |
|
CU |
AL |
mm2 |
mm |
mm2 |
mm |
mm |
kg/km |
mm2 |
mm |
mm |
mm |
mm |
kg / km |
35 |
8 |
16 |
3.1 |
60 |
3750 |
2880 |
6.5 |
1.7 |
2.5 |
3.2 |
74.9 |
9460 |
8700 |
50 |
8 |
16 |
3.2 |
65 |
5240 |
4260 |
6.7 |
1.8 |
3.15 |
3.4 |
79 |
10620 |
9680 |
70 |
8 |
16 |
3.3 |
70 |
6120 |
4730 |
7.1 |
1.8 |
3.15 |
3.5 |
82.5 |
11840 |
10440 |
95 |
8 |
16 |
3.4 |
74 |
7140 |
5240 |
7.5 |
1.9 |
3.15 |
3.6 |
86.4 |
13200 |
11350 |
120 |
8 |
16 |
3.5 |
77 |
8080 |
5710 |
7.9 |
2 |
3.15 |
3.7 |
89.9 |
14520 |
12190 |
150 |
8 |
25 |
3.6 |
80 |
9120 |
6220 |
8.2 |
2 |
3.15 |
3.8 |
93.6 |
16070 |
13280 |
185 |
8 |
25 |
3.7 |
84 |
10440 |
6940 |
8.6 |
2.1 |
3.15 |
3.9 |
97.3 |
17710 |
14090 |
240 |
8 |
25 |
3.9 |
91 |
12620 |
8010 |
9.2 |
2.2 |
3.15 |
4.1 |
103.2 |
20370 |
15460 |
300 |
8 |
25 |
4 |
95 |
14690 |
8800 |
9.7 |
2.3 |
3.15 |
4.3 |
108.2 |
22980 |
17210 |
400 |
8 |
35 |
4.3 |
103 |
17720 |
10230 |
10.3 |
2.4 |
3.15 |
4.5 |
116.8 |
27480 |
19450 |
Electrical Data
Nom.Cross-Section Area |
|
Unarmored Cables |
Aluminium Wire Armoured Cables |
|
Current Ratings |
D C Resistance |
A C Resistance |
Short Circuit Rating of Conductor |
Capacitance |
Charging Current |
Short Circuit Rating of Copper Wire Screen |
Short Circuit Rating of Copper Tape Screen |
Reac- |
Induc-tance |
Ground |
Duct |
Air |
Area |
CU / AL |
CU / AL |
CU / AL |
Per Core 1 sec |
Per Core 1 sec |
tance |
1 sec |
|
|
|
CU |
AL |
CU |
AL |
CU |
AL |
mm2 |
µΩ/m |
µΩ/m |
kA |
pF/m |
mA/m |
kA |
kA |
µΩ/m |
nH/m |
A |
A |
A |
35 |
524/868 |
668/1113 |
5.0/3.2 |
132 |
0.79 |
2.6 |
0.9 |
140 |
460 |
170 |
135 |
155 |
120 |
180 |
145 |
50 |
387/641 |
494/822 |
6.8/4.4 |
142 |
0.85 |
2.6 |
1 |
134 |
430 |
210 |
160 |
185 |
140 |
225 |
175 |
70 |
268/443 |
343/568 |
9.8/6.3 |
159 |
0.95 |
2.6 |
1 |
127 |
400 |
255 |
195 |
225 |
170 |
275 |
215 |
95 |
193/320 |
248/410 |
13.3/8.5 |
175 |
1.05 |
2.6 |
1.1 |
121 |
390 |
295 |
230 |
260 |
205 |
330 |
260 |
120 |
153/253 |
196/325 |
17.2/11.0 |
189 |
1.13 |
2.6 |
1.1 |
117 |
370 |
335 |
260 |
300 |
235 |
380 |
300 |
150 |
124/206 |
159/265 |
21.2/13.5 |
201 |
1.21 |
4.3 |
1.2 |
113 |
360 |
375 |
290 |
335 |
265 |
430 |
335 |
185 |
99.1/164 |
128/211 |
26.6/17.0 |
217 |
1.3 |
4.3 |
1.2 |
109 |
350 |
420 |
330 |
380 |
300 |
490 |
390 |
240 |
75.4/125 |
98/161 |
34.9/22.3 |
237 |
1.42 |
4.3 |
1.3 |
104 |
330 |
480 |
380 |
430 |
345 |
570 |
460 |
300 |
60.1/100 |
80/130 |
43.8/28.0 |
258 |
1.55 |
4.3 |
1.4 |
101 |
320 |
530 |
425 |
480 |
385 |
650 |
520 |
400 |
47.0/77.8 |
64/102 |
57.3/36.6 |
282 |
1.69 |
5.8 |
1.5 |
96 |
290 |
590 |
480 |
520 |
420 |
700 |
570 |