MV Aerial Bundled Conductor ABC Cables Standards:
IEC 60502-2
MV Aerial Bundled Conductor ABC Cables Constructions:
Conductor: Round, Aluminium Conductor
Conductor Screen: Extruded semi-conductive layer.
Insulation: XLPE
insulation Screen: Extruded semi-conductive layer.
metallic Screen(optional): Copper wire screen or copper tape screen.
Separator: Semi-conductive swellable tape.
outer Sheath: HDPE.
Messager wire: Galvanized steel wires.
Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel
wires in a right hand lay.
MV Aerial Bundled Conductor ABC Cables Application:
Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders
to residential premises.
The Function of messenger wire:
A) It acts as load bearing wire. B) It acts as earth or neutral conductor
MV Aerial Bundled Conductor ABC Cables Specifications:
6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables
Number of CoresxNominal Cross Section |
Phase Conductor |
Messenger Suspension Unit |
Continuous current rating at 30ºC ambient temp |
Stranding |
Nominal Sectional Area |
Maximum Conductor Resistance |
Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm2 |
mm |
mm |
mm |
mm |
No.×mm |
mm2 |
KN |
3x35 |
6.9 |
3.4 |
0.8 |
1.2 |
7/4.75 |
52.4 |
1370 |
3x50 |
8.1 |
3.4 |
0.8 |
1.2 |
7/4.75 |
54.6 |
1530 |
3x70 |
9.7 |
3.4 |
0.8 |
1.2 |
7/4.75 |
57.8 |
1790 |
3x95 |
11.4 |
3.4 |
0.8 |
1.2 |
7/4.75 |
61.3 |
2100 |
3x120 |
12.8 |
3.4 |
0.8 |
1.2 |
19/3.50 |
67.3 |
2540 |
3x150 |
14.2 |
3.4 |
0.8 |
1.2 |
19/3.50 |
70.1 |
2840 |
3x185 |
15.7 |
3.4 |
0.8 |
1.2 |
19/3.50 |
73.1 |
3190 |
12.7/22 kV AL/XLPE /HDPE Non-screened Cables
Number of CoresxNominal Cross Section |
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Thickness of Sheath |
Messenger Suspension Unit Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm2 |
mm |
mm |
mm |
mm |
No.×mm |
mm2 |
KN |
3x35 |
6.9 |
5.5 |
0.8 |
1.2 |
7/4.75 |
61 |
1780 |
3x50 |
8.1 |
5.5 |
0.8 |
1.2 |
7/4.75 |
63.3 |
1970 |
3x70 |
9.7 |
5.5 |
0.8 |
1.2 |
7/4.75 |
66.5 |
2260 |
3x95 |
11.4 |
5.5 |
0.8 |
1.2 |
7/4.75 |
69.9 |
2600 |
3x120 |
12.8 |
5.5 |
0.8 |
1.2 |
19/3.50 |
75.9 |
3070 |
3x150 |
14.2 |
5.5 |
0.8 |
1.2 |
19/3.50 |
78.7 |
3390 |
3x185 |
15.7 |
5.5 |
0.8 |
1.2 |
19/3.50 |
81.7 |
3760 |
12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables
Number of CoresxNominal Cross Section |
Diameter of Conductor |
Thickness of Insulation |
Thickness of Insulation Screen |
Copper Wire Screen Stranding |
Thickness of Sheath |
Galvanized Steel Wire Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm2 |
mm |
mm |
mm |
No.×mm |
mm |
No.×mm |
mm2 |
KN |
No.×mm2 |
mm |
mm |
mm |
No.×mm |
mm |
No.×mm |
mm2 |
KN |
Light Duty Screen |
3x35 |
6.9 |
5.5 |
0.8 |
25/0.85 |
1.8 |
7/2.00 |
62.7 |
2280 |
3x35 |
6.9 |
5.5 |
0.8 |
25/0.85 |
1.8 |
19/2.00 |
66.7 |
2580 |
3x50 |
8.1 |
5.5 |
0.8 |
25/0.85 |
1.8 |
19/2.00 |
69 |
2780 |
3x70 |
9.7 |
5.5 |
0.8 |
25/0.85 |
1.9 |
19/2.00 |
72.6 |
3110 |
3x95 |
11.4 |
5.5 |
0.8 |
25/0.85 |
1.9 |
19/2.00 |
76 |
3460 |
3x120 |
12.8 |
5.5 |
0.8 |
25/0.85 |
2 |
19/2.00 |
79.2 |
3810 |
3x150 |
14.2 |
5.5 |
1 |
25/0.85 |
2 |
19/2.00 |
82.8 |
4230 |
3x185 |
15.7 |
5.5 |
1 |
25/0.85 |
2.1 |
19/2.00 |
86.2 |
4650 |
Heavy Duty Screen |
3x35 |
6.9 |
5.5 |
0.8 |
40/0.85 |
1.8 |
7/2.00 |
62.7 |
2510 |
3x35 |
6.9 |
5.5 |
0.8 |
40/0.85 |
1.8 |
19/2.00 |
66.7 |
2810 |
3x50 |
8.1 |
5.5 |
0.8 |
23/1.35 |
1.8 |
19/2.00 |
71 |
3300 |
3x70 |
9.7 |
5.5 |
0.8 |
32/1.35 |
1.9 |
19/2.00 |
74.6 |
3970 |
3x95 |
11.4 |
5.5 |
0.8 |
39/1.35 |
1.9 |
19/2.00 |
78 |
4600 |
3x120 |
12.8 |
5.5 |
0.8 |
39/1.35 |
2 |
19/2.00 |
81.2 |
4950 |
3x150 |
14.2 |
5.5 |
1 |
39/1.35 |
2 |
19/2.00 |
84.8 |
5360 |
3x185 |
15.7 |
5.5 |
1 |
39/1.35 |
2.1 |
19/2.00 |
88.2 |
5790 |
Other cross-sections can be offered upon request.
IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines
Number of CoresxNominal Cross Section |
Phase Conductor |
Messenger Suspension Unit |
Continuous current rating at 30 ambient temp |
Stranding |
Nominal Sectional Area |
Maximum Conductor Resistance |
Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm2 |
No.×mm |
mm2 |
Ω/Km |
No.×mm |
mm2 |
KN |
A |
3X50 + 1X25 |
19/1.78 |
50 |
0.641 |
7/3.0 |
50 |
60 |
116 |
3X70 + 1X50 |
19/.14 |
70 |
0.443 |
7/3.15 |
50 |
62 |
210 |
3X95+ 1X50 |
19/2.52 |
95 |
0.32 |
7/3.0 |
50 |
60 |
173 |
3X185+1X120 |
37/2.52 |
185 |
0.164 |
7/4.67 |
120 |
150 |
259 |
3X150 +1X50 |
37/2.25 |
150 |
0.206 |
7/3.15 |
50 |
62 |
365 |
3X240 +1X50 |
61/2.25 |
240 |
0.125 |
7/3.15 |
50 |
62 |
500 |
IEC 60502 19/33 kV ABC for Overhead Distribution Lines
Number of CoresxNominal Cross Section |
Phase Conductor |
Messenger Suspension Unit |
Continuous current rating at 30 ambient temp |
Stranding |
Nominal Sectional Area |
Maximum Conductor Resistance |
Stranding |
Nominal Sectional Area |
Breaking Load |
No.×mm2 |
No.×mm |
mm2 |
Ω/Km |
No.×mm |
mm2 |
KN |
A |
3X50 + 1X50 |
19/1.78 |
50 |
0.641 |
7/3.0 |
50 |
60 |
165 |
3X150+ 1X50 |
37/2.25 |
150 |
0.206 |
7/3.0 |
50 |
60 |
315 |
3X185+1X70 |
37/2.52 |
185 |
0.164 |
7/3.57 |
70 |
91 |
355 |
3X70 +1X50 |
19/2.14 |
7 |
0.443 |
7/3.15 |
50 |
62 |
250 |
3X150 +1X50 |
37/2.25 |
150 |
0.206 |
7/3.15 |
50 |
62 |
370 |