SAX 10KV XLPE Power cable for overhead lines Constructions:
Conductor: Round, stranded and compacted aluminum conductor
Insulation: XLPE
SAX 10KV XLPE Power cable for overhead lines Standards:
SFS 5791/94
SAX 10KV XLPE Power cable for overhead lines Application:
The aerial bundled cables designed for supply aerial service for temporary service at construction sites, as a service drop (power pole to service entrance),as a secondary cable (pole to pole) or street lighting.
SAX 10KV XLPE Power cable for overhead lines Technical data:
Working Voltage:6/10KV
Test Voltage:21KV
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds): 250°C
Bending radius: 10x Overall Diameter
Parameter:
Nominal cross-section of a conductor |
Number of strands in conductor |
Nominal diameter of conductor |
Nominal thickness of sheath |
Approximate overall diameter |
Mass of cable approx. |
Breaking load min. |
Resistance at temperature 20ºC - max |
Current carrying capacity |
Short circuit current for 1 s |
mm2 |
N |
mm |
mm |
mm |
kg/km |
kN |
Ω/km |
A |
kA |
35Alm |
7 |
7.0+-0.20 |
2.3 |
11.6 |
160 |
11.2 |
0.986 |
195 |
3.2 |
50Aim |
7 |
8.0+-0.20 |
2.3 |
12.6 |
200 |
14.2 |
0.72 |
245 |
4.35 |
70Aim |
7 |
9.7+-0.25 |
2.3 |
14.3 |
270 |
20.6 |
0.493 |
300 |
6.85 |
95Alm |
7 |
11.3+-0.3 |
2.3 |
15.9 |
350 |
27.9 |
0.363 |
370 |
8.908. |
120 Aim |
19 |
12.8+-0.3 |
2.3 |
17.4 |
425 |
35.2 |
0.288 |
425 |
11.7 |
150 Aim |
19 |
14.2+-0.3 |
2.3 |
18.8 |
510 |
43.4 |
0.236 |
495 |
14.5 |
35/ACrm |
7 |
7.0+-0.20 |
2.3 |
11.6 |
205 |
11.2 |
0.986 |
195 |
3.2 |
50/ACrm |
7 |
8.0+-0.20 |
2.3 |
12.6 |
250 |
14.2 |
0.72 |
245 |
4.35 |
70/ACrm |
7 |
9.7+-0.25 |
2.3 |
14.3 |
340 |
20.6 |
0.493 |
300 |
6.85 |
95/ACrm |
7 |
11.3+-0.3 |
2.3 |
15.9 |
450 |
27.9 |
0.363 |
370 |
8.908. |
120/ACrm |
19 |
12.8+-0.3 |
2.3 |
17.4 |
470 |
35.2 |
0.288 |
425 |
11.7 |
150/ACrm |
19 |
14.2+-0.3 |
2.3 |
18.8 |
590 |
43.4 |
0.236 |
495 |
14.5 |
*35/ACrm |
7 |
8.4 |
2.3 |
13 |
245 |
13.38 |
0.778 |
195 |
3.2 |
*50/ACrm |
7 |
9.6 |
2.3 |
14.2 |
305 |
17.01 |
0.595 |
245 |
4.35 |
*70/ACrm |
7 |
11.4 |
2.3 |
16 |
405 |
23.59 |
0.422 |
300 |
6.85 |
*95/ACrm |
7 |
13.5 |
2.3 |
18.1 |
545 |
32.98 |
0.301 |
370 |
8.908 |