Application: | Construction, Overhead, Underground, Industrial |
---|---|
Voltage: | Low and Medium Voltage Cable |
Current: | DC & AC |
AC90 Aluminum Alloy Conductor Interlocked Armoured Cable Construnction:
AC90 Aluminum Alloy Conductor Interlocked Armoured Cable Application:
designed for exposed and concealed wiring such as ventilated cable trays and other dry locations,
where the maximum conductor temperature will not exceed 90°C.
AC90 Aluminum Alloy Conductor Interlocked Armoured Cable Standard:
CSA Spec. C22.2, No. 51 - Armoured Cables
CSA File Listing: LL90458
CSA -40°C Cold Temperature Rating
AC90 Aluminum Alloy Conductor Interlocked Armoured Cable Technical Data:
Rated Voltage: 600V
Maxium Working Temperature:90 º C
Short-circuit max. Conductor temperature:250°C
Bending radius:14D
Packing: steel/wooden reel, wooden reel or steel reel.
Conductor | Bare Bonding Conductor Size (AWG) | Approximate Diameter | Approximate Net Cable Weight | Allowable Amps 30°C Ambient in Conduit | ||||
Size (AWG or kcmil) |
No of Conductors | Insulation Thickness | ||||||
mm | mm | kg/km | 60°C | 75°C | 90°C | |||
14 | 2 | 0.76 | 14 | 11.5 | 134 | 15* | 20* | 25* |
12 | 2 | 0.76 | 14 | 12.4 | 165 | 20* | 25* | 30* |
10 | 2 | 0.76 | 12 | 13.4 | 220 | 30* | 35* | 40* |
14 | 3 | 0.76 | 14 | 12.1 | 162 | 15* | 20* | 25* |
12 | 3 | 0.76 | 14 | 12.9 | 204 | 20* | 25* | 30* |
10 | 3 | 0.76 | 12 | 14.1 | 280 | 30* | 35* | 40* |
14 | 4 | 0.76 | 14 | 13.5 | 193 | 15* | 20* | 25* |
12 | 4 | 0.76 | 14 | 13.8 | 246 | 20* | 25* | 30* |
10 | 4 | 0.76 | 12 | 15.8 | 363 | 30* | 35* | 40* |
3 | 3 | 1.143 | 6 | 26.4 | 1198 | 85 | 100 | 115 |